The ARD3M intelligent motor protector is suitable for low-voltage motor circuits with rated voltage up to 660V and integrates protection, measurement, control, communication, operation and maintenance. Its perfect protection function ensures the safe operation of the motor, with logic programmable function, can meet a variety of control methods. Different communication modules can be selected to meet the needs of field communication.
Technical parameters | Technical indicators | |
Protector auxiliary power supply | Support two power modules, AC 220V power module (AC85-265V/DC100-300V) default, AC 380V power module (AC/DC 100-415V) optional | |
Rated working voltage of the motor | AC220V / 380V / 660V, 50Hz / 60Hz | |
Rated operating current the m tor | 1 (0.1A-5000A) | External cu rent transform |
5 (0.1A-5000A) | ||
25 (6.3A-25A) | ||
100 (25A-100A) | ||
250 (63A-250A) | ||
800 (250A-800A) | ||
Relay output act capacity | Impedance load | AC250V, 10A |
Switching input | 10 channels of passive dry contact (active DC110V, DC220V, AC220V input can be optional) | |
Communication | Standard supplied | 2channel MODBUS RTU communication |
Optional (only one can be selected) | 1-2 channel PROFIBUS DPV1communication, 1channel PROFINET communication, Ethernet communication (MODBUS TCP) protocol) | |
Environment | Working temperature | -10°C〜5 5°C |
Storage m t re | -25°C〜70°C | |
Relative humidity | W95 % No condensation, no corrosive gas | |
Altitude | < 2000m | |
Pollution levels | Class 3 | |
Protection grade | Main body IP20, split display module IP54 (installed on the cabinet panel) | |
Installation category | Level III |
Company | Acrel | Schneider | Siemens | ABB | ||
Series | ARD2M | ARD3M | Tesys T | Simocode pro V | UMC100 | |
Measuring | Current, heat capacity | √ | √ | √ | √ | √ |
Voltage, active power, active energy, frequency | √ | √ | √ | √ | √ | |
Reactive power, reactive energy | √ | √ | √ | × | × | |
Harmonic | 2-21th | 2-63th | × | × | Total Harmonics | |
Leakage current/ground current | √ | √ | √ | √ | √ | |
Positive sequence, negative sequence, zero sequence voltage, current | √ | √ | × | × | √ | |
PTC/NTC | √ | √ | √ | √ | √ | |
PT100 temperature measurement | √ | × | × | √ | External Module 6 ways | |
4-20ma input | × | × | × | External Module, 2 ways | External Module 6 ways | |
Protection | Conventional current protection such as inverse time overload | √ | √ | √ | √ | √ |
Overflow/quick break | √ | √ | × | × | √ | |
tE | √ | √ | × | × | √ | |
Voltage Dependent Protection | √ | √ | √ | √ | √ | |
Leakage current | √ | √ | √ | √ | √ | |
Temperature protection | √ | √ | √ | √ | √ | |
Insulation monitoring | × | √ | √ | × | × | |
Number of starts | √ | √ | √ | √ | √ | |
Event Record | Fault record | 8 | 8 | × | √ | 16 |
Start/stop record | 8 | 8 | × | × | ||
Restart recording | 8 | 8 | × | × | ||
Displacement record | 8 | 8 | × | × | ||
Fault recorder | × | 49 | × | × | ||
Power-on/power-off record | 8 | 8 | × | × | ||
Running record | × | 5 hour | × | × | ||
Control | DI | 8 | 10 | 6(10) | 4(12) | 6(14) |
DO | 5 | 6 | 4 | 3(7) | 4(9) | |
Start control | √ | √ | √ | √ | √ | |
Loss of pressure restart | √ | √ | × | × | × | |
4-20mA output | 1 | 2 | × | 1 | 1 | |
Graphical programming | × | × | √ | √ | √ | |
Communication | Modbus-rtu | 2 | 2 | 1 | × | 1 |
Profibus-dp | 1 | 2 | 1 | √ | 1 | |
Profinet | × | 1(2 ports) | × | √2 ports | 1 (2 ports) | |
ModbusTCP | × | 1(2 ports) | 1 | × | 1 (2 ports) | |
Ethernet/IP | × | × | × | × | 1 | |
Devicenet | × | × | 1 (2 ports) | × | 1 (2 ports) | |
Profisafe | × | × | × | √ | × | |
Can | × | × | 1 | × | 1 | |
Wifi | × | 1 | × | × | × | |
Special | LCD display | 2.4 inch | × | × | × | |
Protocol customized | √ | √ | × | √ | × | |
Zero sequence transformer 30A | × | × | × | √ | × | |
Built-in transformer | 100A | × | 100A | × | 63A | |
USB interface | × | √ | × | × | √ |